Eclipse, 2-4 Conventional or Twin Wire Zones

The Eclipse is a 2 or 4 zone conventional or Twin Wire fire control panel. Even as the entry level panel from Haes, the Eclipse encompasses all of our usual quality, reliability and ease of use attributes to provide a panel that meets a variety of needs.

To buy this product please contact our sales department on 01895 424505

Product Overview

The only entry level panel on the market to reduce false alarms

The Eclipse has been designed to minimise labour costs. There is ample room for wiring, changing batteries and clear indication. Activation is via key switch or access code, which means you should always be able to work on the panel. The one man walk tests will help reduce the cost of maintenance.

The colour coded buttons and the 3 step silence functionality provide simplicity allowing non-technical people the confidence to correctly manage their fire alarm system. Eclipse is the only entry level panel on the market that will reduce false alarms and can be programmed to require a secondary confirmation before sending the panel into alarm.

Two or four fire zone circuits are provided plus two monitored sounder circuits. Fire & Fault VFCO relays, Fire & Fault switched negative outputs, class change and an alert input are also included. The fire zone outputs can be set as ‘Twin Wire’ by DIL switch selection. Eclipse panels are LPCB approved to European standards EN54-2 & 4, Fire Detection and Alarm Systems – Control & Indicating Equipment.

Key features include:

  • 2 or 4 zone
  • False alarm management mode
  • Twin Wire selection by DIL switch
  • Class change and pulsing inputs
  • Fire & fault relays
  • One man walk test

Technical Specification

Main Features

  • 2 or 4 zones
  • Twin Wire, selection by DIL switch
  • Activate controls via keyswitch or code entry
  • Soft tactile buttons for controls & programing
  • Conventionally wired, compatible with most detectors
  • Integral detector removal monitoring
  • 1.25 Amp switch mode power supply Nom 27V DC
  • 2 monitored sounder outputs
  • 2 Aux C/O relays (1 x Fire) (1 x Fault). voltage free
  • Class change I/P
  • Alert I/P
  • Fire & fault switched -ve outputs
  • False alarm mode
  • Test mode, with or without sounders
  • Disable zones, sounder O/Ps & Aux O/Ps
  • Alarm load, 800mA shared between all sounder outputs
  • All sounder circuits are fused @ 500mA with resettable fuses.

External Indications – Level 1

  • Zones in Fire
  • Zones in Fault, Disabled or in Test Mode
  • Supply Healthy
  • General Fire
  • General Fault
  • General Disablement
  • Test Mode
  • Sounder Status
  • Aux Output Status
  • Power Supply Fault
  • System Fault
  • Access Level

External Controls – Level 2

  • Keyswitch or code entry ‘activate controls’
  • Colour coded buttons for controls and programming
  • Button functions:
    • Resound
    • Silence
    • Reset
    • Disable Mode
    • Test Mode
    • Mute Buzzer
    • Test Lamps
    • Enter

Internal Controls

  • PSU Voltage adjustment
  • DIL switches:
    • Twin Wire mode
    • Zone interface setting
    • Access level 3 mode

Access Level 3 Options

  • Select sounder resound options for zones (EN54 requirement)
  • Select Type ‘A’ dependency per zone
  • View / edit dependency functions
  • Initialise factory settings
  • Set buzzer volume
  • Change keypad access code
  • Non latching zones
  • Short circuit as alarm zones
  • Intrinsically safe zones
  • Program O/Ps to cancel on Silence Alarms
  • Program sounder circuit responses

Cabinet

  • Mild steel, lockable, 20mm knockouts
  • Colour ref: Radon MW334E Interpon powdercoat
  • Back box = 300mmW x 250mmH x 80mmD
  • Lid = 308mmW x 260mmH x 23mm (Return)
  • Max battery size = 2 x 3.2Ah, 12v, SLA

Downloads

The following downloads are available for this product:

Eclipse Data Sheet
Eclipse Installation & Commissioning Manual